P/N: ETI0018-1220
DC/AC Power Inverter
3000 VA, 2000
Watts
48 VDC In
Selectable 100/110/120* VAC Out
Features:True sinewave output (THD < 3%)
Power On-Off Remote Control
Input & Output fully isolated
Load control cooling fan
Advanced microprocessor
Output frequency 50/60 Hz selectable
Low power saving mode to conserve energy
Built-in transfer switch & AC circuit breaker
ROF (Remote Override Function) or ignition lockout function option
Speed up transfer time & synchronized operation with utility AC source
Input polarity reverse/ under voltage / over voltage protections
Output short circuit/ overload / over temperature protections
Tri-color indicators display input, output level & failure status
e-13/ CE /FCC approved
Optional 220 /230 /240 VAC Out
Model Numbers: |
|||
AC Output | |||
AC Voltage |
100 / 110 / 120 VAC | ||
Rated Power |
2000 W | ||
Surge Power |
4000 W | ||
Waveform |
True sinewave (THD < 3%) | ||
Frequency |
50 / 60 Hz selectable by DIP switch | ||
AC Regulation |
+/- 3% | ||
Power Factor Allowed |
COS -90° ~ COS +90° | ||
Standard Receptacles |
HARDWARE | ||
LED Indicator |
Input voltage level, output load level & fault status | ||
DC Input |
|||
No Load Current Draw |
2.60A | 1.50A | 0.70A |
Stand-By Current Draw |
0.60A | 0.30A | 0.20A |
DC Voltage |
12 VDC | 24 VDC | 48 VDC |
Voltage Range |
10.5~15.0 VDC | 21~30 VDC | 42~60 VDC |
Efficiency (Typ.) |
88.0% | 91.0% | 92.0% |
Fuse |
40A x 8 | 20A x 8 | 20A x 4 |
Circuit Breaker |
35 A | ||
Synchronous AC Transfer |
Yes | ||
Transfer Switch |
25 A | ||
Transfer Time |
Inverter to utility AC:8~10 msec.: Utility AC to inverter:12~14 msec | ||
Remote Control Unit |
CR6 / CR8 optional | ||
Protection |
|||
Low Battery Alarm |
11 VDC | 22 VDC | 44 VDC |
Low Battery Shutdown |
10.5 VDC | 21.0 VDC | 42.0 VDC |
Over load |
Shut off output voltage, re-power on to recover | ||
Over Voltage |
15.3 VDC | 30.6 VDC | 61.2 VDC |
Over Temperature |
Shut off output voltage, recovers automatically after temperature goes down | ||
Output Short |
Shut off output voltage, re-power on to recover | ||
Battery Polarity |
By fuse opening | ||
Environmental |
|||
Working Temperature |
0 ~ +40° C | ||
Working Humidity |
20% ~ 90% RH non-condensing | ||
Storage Temp. Humidity |
-30° C ~ +70° C / -22° F ~ +158° F / 10~95% | ||
Standards |
|||
Safety Standards |
Meets UL458 | ||
Isolation Resistance |
I/P ~ O/P: 100M Ohms / 500 VDC | ||
EMI & Radiation |
Compliance to FCC Class A | ||
EMS Immunity |
|||
LVD |
|||
e-MARK |
|||
Mechanical |
|||
Dimensions |
433 x 332 x 115 MM (L x W x H) | ||
Packaging |
711.2 kgs; 1 set / 13 kgs / CARTON | ||
Cooling |
Load controlled cooling fan |