View a larger version of one of the small TCD images above

Tan Desk Desk with Inverter
Tactical Desk
with Global AC Power Conditioner

ETI’s Tactical Desks are equipped with a power conditioner (and/or UPS), which are easily installed by replacing the drawers. These power drawers are shaped to duplicate the drawer format including the side drawer glides and front locking hasp. By replacing the drawers, we are able to equip new desks quickly or retrofit your pre-existing Tactical Desks with ETI's tactical power equipment.

The small top left drawer holds a power conditioner taking either global AC and/or vehicle DC in and outputting 120 VAC, 60 Hz to two GFCI outlets. These tactical conditioners feature air flow specially designed to work within the confines of a drawer's space and still stay cool. The power rating for these desks is 500 VA though other power levels are available.
Conditioner & Powerstation

Technical Specifications: Global Power Conditioner
AC OUTPUT
Output voltage: 120 VAC true sinewave std, 220 VAC optional
Output rating: UPS 500 VA/300 Watt  standard,
1000 VA/600 Watt optional
0.60 power factor standard
Non-linear load capacity: Up to 100% non-linear load capability w/o derating
Output voltage regulation: ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: Less than 5.0% into 100% non-linear load
Output frequency: 60 Hz ± 1.0% independent of input frequency, 50 Hz optional
Operational status Status, load and DC input levels (16) LEDs with dimmer
AC INPUT
Input voltage selection: Autoranging from nominal 115 VAC to 230 VAC
Input voltage tolerance: 85-264 VAC
Input frequency: From 47 Hz to 63 Hz
Input power factor: Better than 90% typically
Input/output isolation: 3000 VAC, >120 dB common mode, <1.0 ma leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded circuit breaker, front panel
Input power connection: AMP CPC, 7 pin, locking
DC INPUT
External DC input: Nominal 22 to 32 VDC
External DC control/protection: Guarded circuit breaker, front panel
External DC connector: AMP CPC, 7 pin, locking
DISTRIBUTION PANEL
Output circuits: Two outputs standard, optional configurations
Output protection: GFCI - Ground Fault Circuit Interrupter
Output receptacles: NEMA 5-15R, 3 pin, other options
MECHANICAL
Dimensions ( H x D x W ): 3.75 x14.0 x 12.0 in (95 x 356 x 305 mm)
Mounting Options: Desk, Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight:
500 VA GPC
1000 VA GPC

28 lb. (13 kg) with lift handles front
28 lb. (13 kg) with lift handles front
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, positive pressure, forced air
Cooling air direction: Rear intake, exhaust to front
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -13° to 140° F ambient (-25° to 60° C)
Operating temperature: 14° to 122° F ambient ( -10° to 50° C)
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m), higher optionally
Operating elevation: Up to 10,000 ft (3,048 m), higher optionally
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A & MIL-S-901
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC, Class A; EN55022
OPTIONAL ACCESSORIES
  Emergency Power Off, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Software Interface, 10BaseT Ethernet SNMP/HTTP port

Request a Quote or Product Info.
*(denotes required field)
Contact ETI by mail at:
Energy Technologies, Inc.
219 Park Avenue East
Mansfield, OH 44902-1845
USA

Contact ETI by phone or fax:
Voice: 419-522-4444
FAX: 419-522-4466